To choose compressed air filters, start from the ISO 8573-1 purity class the use needs, then check the order of the filters in the line, the pressure drop and its energy cost, the flow and pressure, the element changes, the condensate drains and whether oil-free air is the better answer.
Ask every compressed air filter supplier the same seven questions, in writing, and compare the answers side by side. The table of filter types follows the checks.
| Check | What to ask the supplier |
|---|---|
| 1. Purity class | Which ISO 8573-1 class does the use need for particles, water and oil? |
| 2. Order in the line | Which filters go before and after the dryer, and where does the carbon go? |
| 3. Pressure drop | What is the pressure drop when new and when loaded, and what does it cost in energy? |
| 4. Flow and pressure | What flow, at what pressure and temperature, in the worst case? |
| 5. Elements | How often are the elements changed, and what tells you when? |
| 6. Condensate drains | How is condensate drained from each separator and filter? |
| 7. Oil-free air | When is an oil-free compressor a better answer than a filter? |
Start from the air quality the process needs, written as an ISO 8573-1 purity class.
ISO 8573-1:2010 (Compressed air: contaminants and purity classes) gives compressed air one purity class for particles, one for water and one for oil, written in that order, such as [2:4:2]. Tell the supplier the three numbers your process needs.
Each number is a different job. Compressed Air Challenge Fact Sheet #11 (May 2026) says particulate filters remove solid particles, coalescing filters remove lubricant and moisture, and adsorbent filters handle vaporous contaminants.
ISO 12500 is the ISO series of test methods for compressed air filters, in four parts: oil aerosols, oil vapours, particulates and water, according to iso.org.
Choose the filters with the dryer: a coalescing filter before a desiccant dryer and a particulate filter after it.
Compressed Air Challenge Fact Sheet #11 (May 2026) says a particulate filter is recommended after a desiccant-type dryer to remove desiccant fines, and a coalescing-type filter before it to prevent fouling of the desiccant bed.
Gardner Denver says its GDWS water separators remove bulk condensed water and liquid oil and are used to protect coalescing filters from bulk liquid contamination.
Activated carbon is a separate stage for oil vapour: the ULTRAK datasheet requires a coalescing filter upstream and recommends a 1 µm dust filter downstream. For a refrigerated dryer, and for where the carbon stage sits in relation to the dryer, ask the manufacturer in writing which filters go on each side.
Five stages, each taking out one thing. Which of them you need depends on the class the air must reach.
Removes bulk condensed water and liquid oil, and protects the coalescing filters downstream.
Removes lubricant and moisture. It goes before a desiccant dryer, to protect the desiccant bed.
Refrigerated or adsorption, chosen for the dew point. Read our guide to choosing a compressed air dryer.
Goes after a desiccant dryer, to remove desiccant fines.
Where oil vapour matters. The ULTRAK needs a coalescing filter upstream, and its datasheet recommends a dust filter downstream.
Compare pressure drop: the dryer and its filters add to the pressure the compressor has to deliver.
Compressed Air Challenge Fact Sheet #4 (May 2026) says that on the supply side air/lubricant separators, aftercoolers, moisture separators, dryers and filters are the main items causing significant pressure drops, and that when selecting filters you should remember that they will get dirty, so dirt loading is also an important selection criterion.
It adds that the maximum pressure drop occurs when the flow rate and temperature are highest, and that the manufacturer of each component should be asked for pressure drop information under those conditions.
The same fact sheet says the pressure rise from resistance to flow can increase the compressor drive energy by 1% of the connected power for each 2 psi (about 0.14 bar) of differential. The US Department of Energy sourcebook (third edition, 2016) gives an example: if a regulator is set at 85 psig and an upstream filter has a pressure drop of 20 psi, the system upstream has to maintain at least 105 psig.
Compressed Air Challenge Fact Sheet #11 (May 2026) says the complete drying, filtration and distribution system should be sized and arranged so that the total pressure drop from the compressor to the points of use is much less than 10% of the compressor discharge pressure.
The ULTRASEC datasheet estimates about 7% of the installed motor power for each extra bar on the compressor, so every bar lost in treatment counts.
Give the manufacturer the air flow, the working pressure and the temperature in the worst case.
A filter’s flow rating is given at stated conditions. Gardner Denver states its GDF flow range of 0.5 to 516 m³/min as a flow rate at 20 °C and 7 bar.
So ask for the flow at your own pressure and temperature, and not only for the figure on the label. The pressure drop is greatest at the highest flow, so ask for it at that flow.
Ask also for the maximum working pressure and temperature of the housing, and check that they are above your own.
Ask how often the elements are changed, and what tells you when.
Compressed Air Challenge Fact Sheet #5 (May 2026) says to replace particulate and lubricant removal elements when the pressure drop exceeds 2 to 3 psid, and to inspect all elements at least annually regardless of the pressure drop indication.
Compressed Air Challenge Fact Sheet #11 (May 2026) words it differently: elements should be replaced as indicated by pressure differential, and at least annually, to minimise pressure drop and energy consumption.
The US Department of Energy sourcebook (third edition, 2016) says filter elements should be changed when the pressure drop approaches the maximum recommended by the manufacturer, and that in many cases the element change is dictated by energy losses.
Ask how condensate is drained from every separator and filter, and how the drains are checked.
Compressed Air Challenge Fact Sheet #5 (May 2026) says a drain trap stuck in the closed position will cause condensate to back up and be carried downstream, and that one stuck open will leak compressed air, so traps need to be inspected periodically.
The US Department of Energy sourcebook (third edition, 2016) lists four ways to drain condensate. It says a timed solenoid valve may not stay open long enough, and opens even when little or no condensate is present, losing compressed air; zero air-loss traps with reservoirs are the fourth method.
Fact Sheet #11 says leaving automatic condensate traps partially open at all times wastes substantial energy and should never be undertaken.
Ask whether an oil-free compressor is a better answer than a filter, and which one the end use needs.
The US Department of Energy sourcebook (third edition, 2016) says lubricant-free air can be produced with lubricant-free compressors or with lubricant-injected compressors that have additional separation and filtration equipment, and that careful consideration should be given to the specific end use, including the risk and cost associated with product contamination.
It adds that the separation and filtration equipment on a lubricant-injected compressor will cause some reduction in efficiency, particularly if the system is not properly maintained.
Oil-free compression is a property of the compressor; a purity class is a property of the air.
Gardner Denver states on its EMEIA website that its oil-free compressors are ISO 8573-1 Class 0 certified, and that its GDFT filter gives ISO 8573-1 Class 1 for total oil when used with water separators and coalescing filters.
The five answers to the question your process asks, side by side.
| Type | What it takes out | Where it goes | What we supply |
|---|---|---|---|
| Water separator | Bulk condensed water and liquid oil | Ahead of the coalescing filters | Gardner Denver GDWS, 0.5 to 200 m³/min |
| Coalescing filter | Lubricant and moisture, including oil aerosol | Before a desiccant dryer, and upstream of an ULTRAK | ULTRADRY inlet filter; Gardner Denver GDF, 0.5 to 516 m³/min |
| Particulate filter | Solid particles, including desiccant fines | After a desiccant dryer | ULTRADRY outlet dust filter; a 1 µm dust filter after an ULTRAK |
| Activated carbon | Oil vapour and other hydrocarbons, by adsorption | After the coalescing filter | ULTRAK, 6 to 6,500 Nm³/h at 7 bar g; Gardner Denver GDFT |
| Oil-free compressor | Keeps lubricant out of the compression chamber, so there is no compressor oil to remove | At the source, in place of added separation | ULTRACECO, and Gardner Denver oil-free compressors |
The ULTRADRY adsorption dryer has a coalescing filter at its inlet and a dust filter at its outlet, and the ULTRASEC refrigeration dryer has a condensate drain with electronic control.
ULTRAK activated carbon towers separate oil vapours from compressed air by adsorption. They come in 24 models, from 6 to 6,500 Nm³/h at 7 bar g and 20 °C.
Ultra Controlo distributes and services Gardner Denver in Portugal, including its compressed air filters, with genuine parts and UltraCare service.
Questions buyers ask us about compressed air filters. More on the medical gas answers page.
To choose compressed air filters, start from the ISO 8573-1 purity class the use needs, then check the order of the filters in the line, the pressure drop and its energy cost, the flow and pressure, the element changes, the condensate drains and whether oil-free air is the better answer.
Send the supplier the flow, the working pressure, the temperature and the three class numbers you need.
The one your process needs, written as one class for particles, one for water and one for oil, such as [2:4:2]. Tell us the three numbers your process needs and we propose the units for that class.
Compressed Air Challenge Fact Sheet #11 (May 2026) says a particulate filter is recommended after a desiccant-type dryer to remove desiccant fines, and a coalescing-type filter before it to prevent fouling of the desiccant bed. The ULTRAK datasheet requires a coalescing filter upstream of the carbon tower and recommends a 1 µm dust filter downstream.
A filter does not use energy itself, but its pressure drop makes the compressor work harder. Compressed Air Challenge Fact Sheet #4 (May 2026) says the pressure rise from resistance to flow can increase the compressor drive energy by 1% of the connected power for each 2 psi of differential.
Compressed Air Challenge Fact Sheet #5 (May 2026) says to replace particulate and lubricant removal elements when the pressure drop exceeds 2 to 3 psid, and to inspect all elements at least annually. Fact Sheet #11 says elements should be replaced as indicated by pressure differential, and at least annually.
A filter takes oil out of the air, and oil-free compression keeps it out. Gardner Denver says its GDFT filter gives ISO 8573-1 Class 1 for total oil when used with water separators and coalescing filters, and that its oil-free compressors are ISO 8573-1 Class 0 certified.
Yes. Ultra Controlo distributes and services Gardner Denver compressors and compressed air filters, and its UltraCare programme covers Ultra Controlo equipment and partner brands. Gardner Denver filters are partner-brand products, not made by Ultra Controlo.
Send us the flow, the pressure, the temperature and the ISO 8573-1 class you need. Our engineering team replies with the filters that fit.