Pharmaceutical plants. Gases that touch the product, specified.

For sterile medicines, EU GMP Annex 1 (2022) says gases in direct contact with the product should be of appropriate chemical, particulate and microbial quality, with oil and water content specified, and that gases in aseptic processes should pass a sterilising grade filter of 0.22 µm maximum at the point of use. Ultra Controlo distributes and services Gardner Denver oil-free compressors, ISO Class 0, which its catalogue lists for pharmaceuticals, and makes ULTRADRY and ULTRASEC dryers, which its brochure lists for pharma.

Tablets in blister packs
01
0.22µm
Maximum nominal pore size of the sterilising grade filter, per EU GMP Annex 1
02
2024
Annex 1 fully applicable since 25 August, per EudraLex Volume 4
03
Class 0
ISO 8573-1 class of Gardner Denver oil-free screw air, per our catalogue
04
−70°C
Lowest ULTRADRY pressure dew point, per our catalogue
Where gases meet the product

Five places the guidance names.

EU GMP Annex 1 (2022) and the US FDA aseptic processing guidance (2004) name these uses of compressed air and other gases in sterile manufacturing.

Annex 1, 6.18

Direct product contact

Gases that touch the product or primary container surfaces; oil and water content are among the parameters to specify.

Annex 1, 6.19

Aseptic processes

Gases filtered through a sterilising grade filter at the point of use, with the pipework after it sterilised and the gas monitored for microbes.

FDA, 2004

Purging and overlaying

The FDA guidance notes that compressed air, nitrogen and carbon dioxide are frequently used for purging or overlaying.

FDA, 2004

Autoclaves, lyophilisers and tanks

Sterile membrane filters for autoclave air lines, lyophiliser vacuum breaks and tanks containing sterilised materials; gas filters should be dry.

Annex 1, 6.20

Vacuum and pressure systems

Where backflow from vacuum or pressure systems poses a risk to the product, mechanisms to prevent it when the system is shut off.

Sources: European Commission, EU GMP Guidelines, Annex 1 Manufacture of Sterile Medicinal Products, C(2022) 5938 final, 6.18 to 6.20; US FDA, Sterile Drug Products Produced by Aseptic Processing (September 2004), section IV.D.

Oil-free or treated air

The texts set the result, not the compressor.

Neither Annex 1 nor the FDA guidance names a compressor type or an ISO 8573-1 class.

EU GMP Annex 1

Specify oil and water

All relevant parameters, including oil and water content, should be specified, taking into account the use and type of gas and the design of the gas generation system.

Source: Annex 1 (2022), 6.18.

US FDA

Appropriate purity

A compressed gas should be of appropriate purity, for example free from oil, with microbiological and particle quality after filtration equal to or better than the air of the environment it enters.

Source: FDA aseptic processing guidance (2004), section IV.D.

Compressed Air Challenge

Two routes to lubricant-free air

Lubricant-free air can come from lubricant-free compressors or from lubricant-injected compressors with additional separation and filtration; weigh the risk and cost of product contamination.

Source: Compressed Air Challenge, Fact Sheet #1 (May 2026).

Annex 1 covers sterile medicinal products. Sources: European Commission (2022); US FDA (2004); Compressed Air Challenge (2026).

Specifying the air

From Annex 1 to the ISO test methods.

Annex 1 asks for the parameters to be specified; the ISO 8573 series gives the methods to measure them, and ISO 8573-1:2010 sets the purity classes.

Sources: European Commission, EU GMP Annex 1, C(2022) 5938 final, 6.18 and 6.19; ISO catalogue, ICS 71.100.20.
ParameterWhat Annex 1 (2022) saysISO 8573 test method
OilSpecify oil content (6.18)ISO 8573-2:2018 oil aerosol; ISO 8573-5:2025 oil vapour
WaterSpecify water content (6.18)ISO 8573-3:1999 humidity; ISO 8573-9:2004 liquid water
ParticlesAppropriate particulate quality (6.18)ISO 8573-4:2019 particle content
MicroorganismsAppropriate microbial quality (6.18); periodic monitoring at the point of use (6.19)ISO 8573-7:2003 viable microbiological contaminants

One supplier. Made and serviced in Portugal.

Ultra Controlo is a Portuguese manufacturer of compressed air, vacuum and technical gas systems, with 40 years of experience. We design, assemble and test our own compressors, dryers and carbon towers in Portugal, and supply and service five partner brands.

Our own lines

ULTRASCREW compressors, ULTRASEC and ULTRADRY dryers and ULTRAK activated carbon towers.

Five partner brands

Gardner Denver, Elmo Rietschle, Thomas, Speck Pumpen (Circutec) and Speck Triplex.

UltraCare, 24/7

Preventive and corrective maintenance, original spare parts and emergency support, by our own team.

Source: Ultra Controlo Industrial 2026 catalogue, pp. 3, 10, 16, 17 and 22.

Questions

Pharmaceutical: questions and answers.

Does EU GMP Annex 1 set an ISO 8573-1 class for compressed air?

No. Annex 1 (2022) says gases in direct contact with the product should be of appropriate chemical, particulate and microbial quality, with all relevant parameters, including oil and water content, specified (point 6.18); it does not name an ISO 8573-1 class.

What filter does Annex 1 ask for on gases in aseptic processes?

A sterilising grade filter with a nominal pore size of 0.22 µm maximum at the point of use (Annex 1, 6.19), integrity tested where it is used on a batch basis or as a product vessel vent filter.

Does Annex 1 require oil-free compressors?

Annex 1 does not name a compressor type; point 6.18 asks that oil and water content be specified, taking into account the use and type of gas and the design of the gas generation system.

Does the FDA guidance require oil-free compressed gas?

The 2004 FDA aseptic processing guidance says a compressed gas should be of appropriate purity, giving free from oil as an example, with microbiological and particle quality after filtration equal to or better than that of the air in the environment it enters.

When did the current Annex 1 come into operation?

The European Commission adopted Annex 1 on 22 August 2022 (C(2022) 5938 final); it came into operation on 25 August 2023, with point 8.123 following on 25 August 2024, and EudraLex Volume 4 lists it as fully applicable since then.

Tell us about your plant.

The products, the points where gas meets them, the pressure and the hours per day. We reply with the equipment that fits.